AC
POWER SUPPLY / FREQUENCY CONVERTER
• Switching
• Linear
INVERTER
UNINTERRUPTIBLE POWER SUPPLY (UPS)
MODIFIED STANDARD PRODUCTS
COTS CUSTOM POWER SUPPLY
• AC-DC
• DC-DC
RAILROAD SIGNAL SOURCE
NEW PRODUCTS
APPLICATION NOTES
WILD FREQUENCY INFORMATION CENTER
|
 |
INVERTER DC
- AC Power Supply
|
INV1200 and INV1210
DC/AC Inverter,
produces AC Power from your DC source or Battery bank
|
|
|
Behlman's
INV series, INVERTERS deliver 1200 VA of 120 Vac,
60 Hz power in a 3.5 inc. high rack mount chassis. The Inverters
operate from either 48 Vdc, 125 Vdc or 250VDC. You have a choice
of a low distortion, sinewave output, Model INV1200 or a well
regulated quasi-sinewave output, Model INV1210.
|
|
FEATURES
-
1200 VA in a 3.5"
high chassis
-
Sinewave or Quasi-Sinewave
Output, Isolated and Floating
-
100% of Rated
Power into any Power Factor Load.
-
-
Excellent Line
& Load Regulation
-
Custom
output frequencies for frequency converter / frequency conversion
applications (consult factory).
-
Option Bypass, DC to AC with Alarms and Indicators or AC to DC.
|
Click
here for Printable Specifications Sheet.
|
SPECIFICATIONS
|
|
INPUT
|
|
MODELS
|
INV-1210-48
|
INV-1210-125
|
INV-1200-250
|
| INPUT |
48 VDC +/-
20% |
125 VDC +/- 20%
|
250 VDC
+/- 20% |
| |
-
Quiescent DC
current drain less than: 2 Amps @ 48 VDC,
1 Amp @ 125 VDC,
0.5 Amps @ 250 VDC.
-
Maximum DC burden
(full load): 40
Amps DC @ 38 VDC,
15 Amps DC @ 100 VDC,
7.5 Amps DC @ 200 VDC.
-
Connections:
Barrier type terminals with #8 screws.
|
|
OUTPUT
|
|
Voltage:
|
120 VAC +/- 5%,
60 Hz +/-.01%
|
|
Current:
|
10 Amps
|
|
Power:
|
1200VA
|
|
Waveform:
|
Sine Wave Output
(Model INV1200)
Modified Sine Wave Output (Model INV1210)
|
|
Power Factor:
|
100% of rated output
into any power factor load.
|
|
Distortion:
|
< 3% THD typical
( Model INV1200 )
|
|
Efficiency:
|
80% typical
|
|
Connection:
|
Two NEMA 5-15 receptacles.
Option -TB: Barrier terminals.
|
|
PROTECTION CIRCUITS
|
|
Input:
|
Main circuit beaker,
Option i: Fuse.
|
|
Short Circuit
Protection:
|
Short circuit overload
electronically latches output to protect load.
|
|
Thermal Protection:
|
Internal temperature
sensor prevents heat damage.
|
|
FRONT PANEL CONTROLS
and INDICATORS
|
|
Power On/Off circuit
breaker
|
|
Three LED's:
DC IN, AC IN, AC OUT . ( With Option D1 or A1 )
|
|
MECHANICAL SPECIFICATIONS
|
|
Dimensions:
|
High strength table
top chassis, 3.5"H x 17.00"W x 17.00"D.
|
|
Weight:
|
25 lbs, Option
|
|
ENVIRONMENT SPECIFICATIONS
|
|
Operating Temperature:
|
0 to 55 C.
|
|
Humidity:
|
Up to 95% non-condensing
|
|
SWC:
|
Designed to meet
IEEE C37.90.1.
|
|
Fast Transient:
|
Designed to meet
IEEE C37.90.1.
|
|
EMI:
|
Designed for immunity
to conducted & radiated EMI.
|
|
RFI:
|
Designed to meet
IEEE C37.90.2 - 1997.
|
|
OPTIONS
|
|
D1
|
AC Input, with Indicators
and Alarms.
DC input primary. Includes AC input with "Transfer Circuit"
to switch from DC to AC, in 2 msec. typical, upon loss of DC
input or Inverter. Includes AC fuse, (3) indicators and (3)
form "C" contacts for AC IN, DC IN and Inverter ON.
|
|
A1
|
Same as Option D1
except AC Mains is primary input with "Transfer" to
DC input upon loss of AC.
|
|
TB
|
Barrier type terminals,
#6 screws
|
|
 |
 |