UNINTERRUPTiBLE POWER SUPPLY
UPS / FREQUENCY CONVERTER

RUPS1250
UPS

  • True On-line UPS- No break in power

  • Hot-swappable batteries

  • Cold start- start on DC capability

  • RS-232 interface

  • Alarms with contact closure

  • Frequency conversion capability

The Behlman RUPS-1250 Uninterruptible Power Source is a true on-line UPS that continuously conditions incoming power and provides a high quality sine wave output with very low distortion. In the event of a loss of input power the RUPS will switch to the internal batteries, in ZERO time, for a safe shutdown.

The RUPS continuously monitors status, input, battery conditions, fault conditions and alarms. This information is displayed on the front panel and can be communicated to a host via a built-in RS-232 interface and relay contact closures.

The RUPS-1250 is a rugged, compact rack-mountable unit, with hot-swappable batteries (from the front panel). The RUPS can "cold-start" (start on DC) and has the ability to output a frequency different from the source frequency. The RUPS-1250 is ideal for remote and difficult-to-access locations. It provides conditioned and back-up power for control, computer, instrumentation, communication and other power sensitive equipment.

The RUPS-1250 can be used anywhere in the world and is an exceptional device for industrial and military ground, aerospace and shipboard applications.

 

Click here for printable Specifications Sheet

 

Specifications
Power:
1200VA / 1000W
Input
Voltage:
95-270 VAC, single phase
Frequency:
45-450Hz

 

Output

Voltage:
115 VAC, +/-2%
Frequency:
50Hz, 60Hz or 400Hz +/-0.1%
Current:
10.9 Amps
Waveform: Pure Sine-wave
Crest Factor:
3:1
Power Factor:
100% of rated output into any power factor load.
Distortion:
< 3% THD typical (with linear loads)
Load Regulation:
+/-2.0% No load to full load
Line Regulation:
+/-0.5% for +/-10% line change
Efficiency: 
 80% Typical (AC-AC)
Switch Over Time: Zero, AC-AC, DC-AC

 

Protective Circuits

Input:
Main circuit breaker
Output:
Fuse (rear panel)
Constant Current:
Overload automatically causes voltage foldback to provide maximum current without distorting output waveform. 
Short Circuit Protection:
Short circuit overload electronically latches output open to protect load. Power restored by cycling input power. 
Thermal Protection:
Two internal temperature sensor. First sensor sounds alarm and second sensor shuts off output to prevents heat damage
Batteries:
Fuse (in battery chassis)
Surge:
IEEE C62.41-1980
ESD:
Withstand capability: IAW IEC 801.2, level 4

 

 

Controls / Indicators

Input Power:
ON/OFF Circuit breaker with guard, locking pin and Green LED

Output:

ON/OFF Circuit breaker with guard and Green LED

Battery:
ON/OFF Switch with guard to turn battery OFF before replacing Battery Module
Display:
24 characters X 2 line vacuum-fluorescent display, providing the following data:
Volts (V), Amps (A), Frequency (F), Watts (W), Power Factor (PF), Battery Voltage (B) and Faults (see Table 1)

Remote Interface:

RS-232 interface for monitoring of operating status and alarms

Alarm Silence:
Momentary switch to turn OFF alarm

 

TABLE 1
FAULT/ALARM
DISPLAY

ALARM SILENCE

Momentary switch

CONTACT CLOSURE

3 form "C" contacts

OUTPUT

STATUS

Line Fail
(LF)
YES
Line Fail
ON
Over Voltage
(OV)
NO
FAULT
OFF
Constant Current
(CC)
YES
FAULT
ON
High Temperature
(HT)
YES
FAULT
ON
Over temperature
(OT)
NO
FAULT
OFF
Overload Latch
(OL)
NO
FAULT
OFF
Low Battery
(LB)
NO
Low Batt

ON

for limited time

 

Batteries (Removable, Hot-swappable, Module

Type:
Sealed, Maintenance free, Lead acid (four, 12V each)

Run Time:

5 minutes typical at full load

Recharge time:
4 hours to 90% of full charge
Cold-Start:
Start on battery without AC input

 

Mechanical & Environmental

Chassis:

High strength rack-mount chassis with handles front & rear

Dimensions:
7.00" H x 19"W x 21"D (17.8 cm X 48.3cm X 53.3 cm)
Weight:
48 lbs (21.8 Kgs)
Input Connector:
J1- MS3400D16-10D
Output Connector:
J2- MS3400D16-10E
Data/Alarms Connector:
J3- DB-15
Battery Connector:
J4- MS3402E-20-23S
Ground Stud:
#10-32
Slide provisions:
Mounting provisions compatible with General Devices CTHRS-122
Operating Temperature:
-4 Deg to +122 Deg F  (-20 Deg to 50 Deg C)
Storage Temperature:
-40 Deg to +149 Deg F  (-40 Deg to 65 Deg C)
Humidity:
Up to 90% non-condensing
Altitude:
Non-operating: 40,000 ft
Cooling:
Internal fans, air-flow front to rear
Designed to meet the following:
MIL-STD-1399
MIL-STD-810D:

Vibration: Method 514.4, Category 5

Shock: Method 516.4, Procedure 1

MIL-STD-461
MIL-STD-704
 

 

Options
BM2:
Battery Module for 15 minutes run time (typical)
BS:
Battle Short - overrides OT shut down. Audible alarms stays ON
EB4:
External Battery chassis (four 12V,21 A/Hr)
S:
Slides

 


Headquarters:
80 Cabot Ct.,
Hauppauge, NY 11788
TEL (800) 874-6727 - (631) 435-0410
FAX (631) 951-4341


West Coast:
2363 Teller Road / Suite 108,
Newbury Park, CA 91320
TEL (800) 456-2006 - (805) 375-7046
FAX (805) 498-2147

Easy Payment, We accept:
MasterCard, Visa, Discover,
American Express

About Behlman | Select a Product | Catalog Request | Support | GSA | Sales/Reps | Orbit Int'l | Home
AC Power Supply/Frequency Converter: SwitchingLinear | Inverters | UPS | Modified Standard Products
COTS: AC-DCDC-DC | Railroad Signal Source | New Products | Application Notes | Wild Frequency Information Center